NFPA 101 Door Locking Compliance and Monitoring Solutions in Healthcare

By Andrew Erickson

June 2, 2025

For healthcare facilities, protecting people is a multi-layered mission. Patients need secure environments that account for their physical safety, cognitive health, and medical conditions.

At the same time, those facilities must remain compliant with NFPA 101 Life Safety Code. This code has long emphasized one critical principle: people must be able to exit during an emergency.

At first glance, these two priorities - security and life safety - are obviously in tension and may seem incompatible. How do you lock a door for patient security without impeding an evacuation during a fire or other emergency?

That's the question that NFPA 101 has been working through for years. A recent article by NFPA's Valerie Ziavras provides a detailed look at the Life Safety Code's rules for door locking in healthcare occupancies.

Now, we'll take a look at:

  • Why locking doors in healthcare settings is sometimes necessary
  • What NFPA 101 allows - and under what conditions
  • Where common missteps occur
  • How continuous monitoring supports both compliance and patient care
  • Why remote monitoring systems are an important part of that equation
Door locking for security

Locked Doors Are Sometimes Necessary

Hospitals and long-term care facilities aren't just about treatment. They're about safety and containment, especially in high-risk units.

Certain patients, due to cognitive decline, psychiatric disorders, or even legal status, may pose a risk to themselves or others if left unmonitored or unrestricted.

In these settings, secured units serve essential purposes:

  • Preventing elopement in memory care or Alzheimer's units
  • Protecting infants from abduction in maternity wards
  • Containing high-risk individuals in psychiatric or detention-based healthcare settings
  • Limiting access to controlled areas like pharmacies or sterile storage

While security systems like access control help manage these risks, they also intersect directly with fire safety rules. That's where NFPA 101 steps in - establishing a nuanced framework that permits door locking in specific circumstances. This is only permitted, though, if the system enables fast, safe evacuation during emergencies.

NFPA

NFPA 101 Mentions Locking Doors

A common myth persists that NFPA 101 prohibits locking any door. In fact, the code only restricts locking on means of egress (routes people would use to evacuate during a fire or emergency).

Doors that aren't part of the required egress path (such as janitor closets, equipment rooms, or secure medication areas) can be locked as needed. The challenge comes when security needs intersect with required egress paths - like exit corridors or patient room doors.

To address this, NFPA 101 allows two major types of special locking arrangements in healthcare facilities:

1. Door Locking for Clinical or Security-Driven Patient Needs

NFPA 101 permits locking doors in required egress paths when a patient's clinical needs require specialized security. This covers situations like:

  • Psychiatric wards, where patients may lack the awareness to navigate the building safely
  • Alzheimer's or dementia units, where getting out can lead to harm or fatality
  • Detention medical units treating prisoners, where escape poses security risks to others

But these allowances come with conditions. The locking system must:

  • Use only one lock per door
  • Provide a way for staff to rapidly release the lock in an emergency

Acceptable unlocking options include:

  • Remote unlocking controls located within the same smoke compartment
  • Staff carrying keys at all times
  • Other reliable unlocking means accessible to authorized personnel at all times

In addition, disguised doors (such as those with murals) are allowed, particularly in memory care environments where seeing an exit may trigger distress. These murals must not obstruct:

  • The exit sign
  • Door handles or panic hardware
  • The required vision panel, if applicable
  • The functional operation of the door

Fire safety plans must clearly identify these doors and include staff training on their location and operation. If the door is a fire-rated door, any modifications - such as added murals or surface treatments - must comply with NFPA 80.

2. Door Locking for Special Protective Measures (e.g., Infant Security)

The second locking exception applies to areas requiring special protective measures for patient safety, such as:

  • Maternity wards (to prevent infant abduction)
  • Pediatric units (to prevent unsupervised wandering)

These scenarios often require fail-safe electrical locks. These automatically unlock in the event of power loss or activation of the fire alarm or sprinkler system.

The electrical hardware must be UL-listed and installed in compliance with manufacturer requirements. NFPA 101 further mandates automatic sprinkler protection for:

  • The smoke compartment housing the locked area
  • Adjacent compartments on the same floor
  • Compartments leading to exits

The code goes on to mention that the locking system must include either:

  • A smoke detection system that triggers lock release and staff carry keys or have access to unlocking controls, or
  • A single lock per door and the ability to remotely unlock all affected doors from a normally attended location, such as a nurse's station

By requiring redundancy and fail-safe defaults, these provisions make sure that no patient is locked in when smoke, heat, or power disruption is detected.

Systems Are Only as Safe as They Are Supervised

Even when door locking systems are code-compliant on paper, real-world failure can happen due to:

  • Power outages that go unnoticed
  • Faulty relays that prevent remote unlocking
  • Staff being unaware of system failures until it's too late
  • Tampering or unreported device malfunctions
  • Poor integration between fire alarm systems and door control modules

The truth is, compliance isn't a set-it-and-forget-it achievement. These systems require continuous supervision and regular status reporting. This is especially true in care environments where people may not be able to exit independently.

And that's where fire and security monitoring systems become essential.

Digitize Supports Code-Compliant Door Locking in Healthcare

Digitize equipment is designed specifically for high-stakes environments like hospitals, secure treatment centers, and behavioral health facilities. Systems like the Prism LX and associated interface modules bridge the gap between NFPA compliance and operational visibility. The system delivers exactly what facility managers and safety officers need:

Real-Time Supervision of Locking Systems

With the correct accessories custom-selected for your building/campus, Prism LX can monitor relays, fail-safe locks, and zone-specific access points in real time - flagging issues the moment they occur.

  • Relay status: is your lock release mechanism still operational?
  • Zone faults: has a power failure or tamper event occurred in the affected smoke compartment?
  • Input conditions: has the sprinkler system or smoke detection loop triggered a door release?

Programmable Logic for Custom Scenarios

In healthcare facilities, your system must be partially customized for your systems and layout. Prism LX offers programmable logic functions, allowing you to configure:

  • Time-delayed releases (if permitted by code)
  • Simultaneous release of all doors in a wing
  • Door unlock triggers tied to specific smoke detector inputs or water flow sensors

This flexibility helps you align both security policy and fire code within a single interface.

Centralized Alerts and Visual Dashboards

During an emergency, staff don't have time to check multiple panels across a building. With Digitize systems:

  • All alerts - fire, trouble, supervisory, or security-related - can be viewed from a central location
  • Events are logged, timestamped, and tagged by zone
  • Color-coded indicators help prioritize actions

Whether your team is responding to an egress issue, a door stuck in locked mode, or a fire alarm from a maternity ward, they have immediate clarity on what's happening and what needs to be done.

Legacy System Integration

Digitize is known for our expertise in retrofitting legacy systems. Many older facilities may already have standalone fire panels or outdated door lock controllers. Rather than replacing everything - a costly and time-consuming process - Digitize can integrate:

  • Older fire panels with modern supervisory platforms
  • Access control or security systems into central monitoring
  • Analog inputs from door sensors and relays into Prism LX's digital infrastructure

This integration means you don't have to choose between cost and compliance. You can have both.

Locking Doors Shouldn't "Lock Out" Safety and Compliance

NFPA 101 recognizes that healthcare is unique. Doors may need to remain locked for good reasons - but they must still unlock fast when lives are on the line. That delicate balance is possible, but only when the systems that control those doors are monitored continuously, not occasionally.

Without real-time alerts, fault reporting, or actionable dashboards, even a well-designed system can become a liability.

Digitize gives you the tools you need to make sure that never happens.

Let's Talk About Your Facility

If you're managing a healthcare facility - or any building where life safety and secure egress must coexist - you owe it to your staff, patients, and inspectors to make sure your systems meet code. Plus, you are required to continuously meet fire code every day.

Digitize is here to help you:

  • Interpret NFPA 101 requirements in practical, enforceable terms
  • Retrofit your existing fire and door control systems into a modern monitoring framework
  • Train staff on how to respond to alerts and maintain readiness
  • Deliver documentation, logging, and evidence of compliance for AHJ inspections

Call us today at (973) 663-1011
Or email info@digitize-inc.com to schedule a quick online meeting

Andrew Erickson

Andrew Erickson

Andrew Erickson is an Application Engineer at DPS Telecom, a manufacturer of semi-custom remote alarm monitoring systems based in Fresno, California. Andrew brings more than 18 years of experience building site monitoring solutions, developing intuitive user interfaces and documentation, and...Read More