System 3505 Prism LX with USB Keyboard

Product Information

System 3505 Prism LX

System 3505 Prism LX

The System 3505 Prism LX™ is a highly integrated alarm monitoring system that uses state-of-the-art components and circuitry to continuously monitor and display the status of all connected alarms. When an alarm condition occurs, the System 3505 Prism LX™ presents it to the operating personnel via a programmable System 3505 Prism LX™ Monitoring System audible alarm, color graphic display and a permanent printed record on the thermal paper tape. The System 3505 Prism LX™ can monitor up to 500 active alarm points simultaneously, and in any combination of multiplex, telegraph / McCullough codes, direct-wire, digital dialer, network, polling radio, and serial input alarm signals, as well as Ethernet utilizing the AlarmLan. Options can be tailored to your installation’s precise needs.

System 3505 Prism LX™ Enhancements

Remote Annunciator offers an interactive audio/visual display of System 3505 Prism LX™ activity at remote locations. Multiple Remote Annunciators can be added to the system, distributing filtered information to many locations. Remote Annunciator options include automatic Text-2-Cell & E-mail notification. See Cut sheet 750581.

Digitize AlarmLan™ option allows the System 3505 Prism LX™ to communicate with equipment practically anywhere in the world via Ethernet. Multiple Prism LX units can be connected in a LAN / WAN configuration and each Prism LX unit becomes an Alarm Server.

Test Mode Option masks user specified alarms by alarm point, groups of alarm points, or buildings, for a user specified time not to exceed 8 hours.

Features

  • 1 GHz Fast Dual Core Cortex A7 ARM Processor – actually has two ARM processors sharing the work load at the same time.
  • Multitasking Linux operating system.
  • 4 Gigabytes of user memory – No longer requires MEM600 chips.
  • Informative 5.7” Color LCD Display with wide angle viewing, very bright!
  • On line programmable.
  • Low Power – Very efficient, no fans.
  • Graphic Thermal Printer provides continuous hard copy printout.
  • External USB Keyboard for user text entry and System setup. Text can be edited via the WIN3505 application and the output file uploaded via the system’s built in WEB browser without interrupting the operation of the Prism LX.
  • Operates in a Standalone mode, or can be part of a LAN / WAN of other Prism LX units via the AlarmLan option.
  • 8 levels of Alarm Priority, 4 are user programmable.
  • Multiple communication protocols utilizing Ethernet, RS-232, RS-485, Radio, & MM/SM Fiber. Configurations are based upon installed options.
  • Extensive programmable sound & volume combinations through the internal sound generator.
  • System operation is supervised. Internal monitor activates an audible alert in the event of an internal malfunction.
  • Customizable – Operation can be modified for user specific applications.
  • ETL & CSFM Listed

Specifications

Dimensions: Height: 6.97" (17.7 cm), Width: 19.0" (48.3 cm), Depth: 15.5" (39.5 cm)

Weight (approximate): Net Weight: 21.3 lbs. (9.7 Kg); Shipping Weight: 25.0 lbs. (11.38 Kg)

Environment: Operating Temperature: 32 to 120° F (0 to 49° C); Storage Temperature: 14 to 158° F (-10 to 70° C); Operating Humidity: 0 to 85% (non-condensing); Storage Humidity: 0 to 85% (non-condensing)

CPU: 1 GHz Dual Core Cortex A7 ARM Processor

Memory: 1 Gigabyte Ram; 4 Gigabytes On Board Flash; 32 Gigabytes External Flash on removable MicroSD memory card. Provides for over 30,000 screens of alarm information.

Display: Resolution: 640 x 480 pixels, VGA; Viewing Area: 5 in. x 3.87 in.; Panel Type: a-Si TFT-LCD LED Backlit; Colors: 262K (6 bit)

Thermal Printer: Print speed: 75mm/s; Roll Size: 3 1/8 in. W x 220 ft. L; Print Image: Black (based on paper used); Capacity: 1500 Alarms per roll

Fuses: AC Line Input Fuse: 3.0 Amp (fast blow)

Power: Primary AC Power Input: 90 to 240 VAC; AC Power Consumption: 100 Watts (max.); Frequency Input: 47-63 Hertz Standby DC Power Input: 24 VDC (nom.); DC Operating Current: 1.5 Ampere DC (max.)

Outputs:

Audio Out: Line level output (1 Volt P-P) for connection to an external amplifier or PA system;

SST Fast: Normally open/closed dry contacts used for special options;

SST Slow: Normally open and normally closed “dry” relay contacts used for special options.

ALARM: Energized based on SET MENU selection;

TROUBLE: Normally energized when System operates properly;

SUP: Energized based on special options;

POWER 1&2: To power additional Digitize equipment

Inputs:

AC Power: Detachable Cord;

Standby Battery: 24 Volts DC (Typically connected to SEBB-LCD Backup charger);

Remote Inputs: “Telegraph Coded Input” option; EXT Inputs 1-6: EXT 4, 5, and 6 are supervised;

CHARGER Fail Supervised Charger Fail Input. (Not needed with SEBB-LCD);

Ethernet: Built in Ethernet port for managing firmware and user memory;

USB Ports: 3 USB Ports, one on front panel, one on rear panel, for connection to USB keyboard. The third port (located inside printer door) allows field service technicians to tether to the 3505 for field updates and servicing.

Applicable Publications: FCC Rules and Regulations, Part 15; National Electric Code; NFPA 72 (Proprietary and Central Station)