Each identification
module contains processor, ROM, RAM, and EEPROM for field updating
of variables such as addresses, etc.
The ID modules include:
Q-EOL
Addressable module for monitoring dry contact closure. Requires
user supplied 1.43 K-ohms resistor for supervision across input
contacts. This is the required module for monitoring fire alarm
contacts.
Q-1R ID module
Q-1R Addressable module that provides magnetically latching relay
contact output under control of the System 3500/3000 via Q-Mux Node.
Relay activation is maintained without power. If Q-Mux system is
reset, relay will return to Normal state.
Q-1C
Digital addressable module for monitoring dry contact closure. No
EOL resistor required.
Q-I/O
Addressable module that combines features of the Q-1C with an open
collector output transistor that may be used to control an indicator
LED. No EOL resistor required.
|